Stokka Brannteknikk

Talentum® UV/IR2 - Flame Detector Range

Ta kontakt for pris

Talentum UV/Dual IR Brochure (English) PDF

These flame detectors give the highest immunity to false flame sources both indoors or out. They have internal self-test sources that check the detector’s operation when remotely instructed. The maximum ambient temperature is normally 55°C or 85°C for the higher temperature specification detectors.

Key Features

  • Highest immunity to false sources
  • Suitable for indoor and outdoor areas
  • Detects invisible flames from fuels such as Hydrogen and other inorganic fuels
  • Selectable response speed
  • Optical self-test
  • Low power consumption
  • Approved to EN54-10:2002

Applications

  • Aircraft Hangars
  • Engine Rooms
  • Engine Test Facilities
  • Generators
  • High Voltage Equipment
  • Nuclear Industry
  • Power Plants
  • Storage Tanks

Standard Models

Standard Dual IR Flame Detector

16591: Die cast zinc alloy
16531: Stainless Steel
16291: Die cast zinc alloy - High Temperature

 

CE Logo - Click to view certificate

 

Hazardous Area Models - Flameproof (Exd)

Flameproof (Exd) Dual IR Flame Detectors

16521: Copper free aluminium allow - Colour red
16221: Copper free aluminium alloy - High Temperature up to 85°C - Colour Red
16561: Stainless Steel - Colour Natural

CE Logo - Click to view certificate

The sensor housings have been certified by ISSeP (notified body no: 492) for compliance with standards EN50014, EN50018 and EN50281.
ISSeP Certificate No.: ISSeP03ATEX012X
Certified to:
ATEX: EX LogoII 2 G D; Zones 1, 2, 21 or 22
CENELEC/IEC: EEx d IIC T6 (85°C); IP66
 

Stainless Steel Housing