Ta kontakt for pris
Talentum Triple IR Brochure (English) PDF
These flame detectors give excellent immunity to false flame sources both indoors or out. They have internal self-test sources that check the detector’s operation when remotely instructed.
They can operate on a conventional 2-wire (14-28 Vdc) fire systems or 4-20mA process control systems. Relay contacts are also available for Fire and Fault signals. The detectors’ operating modes can be user selected giving a choice of alarm currents, response times, latching or non-latching outputs and sensitivity. The detectors have a maximum ambient operating temperature of 55°C.
Key Features
- Excellent immunity to false sources
- Suitable for indoor and outdoor areas
- Detects invisible flames from fuels such as Hydrogen and other inorganic fuels
- Selectable response speed
- Optical self-test
- Low power consumption
- Approved to EN54-10:2002
Applications
- Atria
- Coal Handling
- Pharmaceuticals
- Printing
- Spray Booths
- Nuclear Industry
- Waste Tips
- Storage Tanks
- Tunnels
Standard Models

16589: Die cast zinc alloy
16509: Stainless Steel

Hazardous Area Model - Intrinsically Safe (IS)

16579: Die cast zinc alloy

The requirements of Directive 94/9/EC, the ATmosphere EXplosives ATEX Directive have been met.
Apparatus Certificate Number: BAS02ATEX1001
System Certificate Number: Baseefa08Y0078 Certified to:
ATEX:
II 1 G
CENELEC/IEC: Ga Ex ia IIC T4; Zones 0, 1, 2
Ex II 1 G Ga Ex ia IIC T4
Zones 0, 1, 2Zones 0, 1, 2
Hazardous Area Models - Flameproof (Exd)

16519: Copper free aluminium allow - Colour Red
16219: Copper free aluminium alloy - High Temperature up to 85°C - Colour Red
16549: Stainless Steel - Colour Natural

Baseefa ATEX Certificate No: Baseefa08ATEX0270
Baseefa IECEx Certificate No: IECEx BAS 08.0073
Ex II 2GD Ex d IIC T4 Gb
Ex tb IIIC T135ºC Db IP66 A21 (Tamb -40ºC to +125ºC)

Stainless Steel Housing